| dc.contributor.author | EJIGA, JOSEPH | |
| dc.date.accessioned | 2021-11-16T08:11:47Z | |
| dc.date.available | 2021-11-16T08:11:47Z | |
| dc.date.issued | 2021-07 | |
| dc.identifier.uri | http://196.220.128.81:8080/xmlui/handle/123456789/4882 | |
| dc.description.abstract | In this research, the Federal University of Technology Akure 33/11 kV Injection Substation Network has been considered under the presence of a distributed generation (DG). The transformer and line data such as phase voltages, line currents, length of transmission and distribution lines, line impedances, line reactances and conductor size were used in the analysis using Newton Raphson Load Flow Algorithm in a computer software called Electrical Transient Analyzer Program (ETAP 12.6.0). The obtained results from the simulation show that the present state of the network is not satisfactory due to low voltage profile, heavy bus loading and high power losses across the branches of the network. A total power of 7.9 kVA at 0.8 leading power factor was injected into the system on simulation without the DG out of which a total power loss of 5.2 kVA at 0.76 leading power factor was observed. The integration of the 50 MW capacity DG unit at the reference bus (Bus1) reduced the power loss to 4.5 kVA at 0.8 leading power factor; the integration of the DG at optimal location (Bus3) further reduced the power loss to 4.2 kVA at 0.8 leading power factor. The minimum bus voltage of 2.91% was recorded with DG, 2.50% without the DG and 2.97% with the DG at the optimal searched location. The range of voltage deviation was found to be between 2.19% and 13.57% at the 11/0.415 kV substations | en_US |
| dc.description.sponsorship | FUTA | en_US |
| dc.language.iso | en | en_US |
| dc.publisher | The federal university of technology,Akure. | en_US |
| dc.subject | 33/11 kV Injection Substation Network | en_US |
| dc.subject | Electrical Transient Analyzer Program (ETAP 12.6.0). | en_US |
| dc.subject | An electric power system | en_US |
| dc.subject | conventional concept of power systems | en_US |
| dc.subject | renewable generation | en_US |
| dc.title | DETERMINATION OF THE EFFECTS OF DISTRIBUTED GENERATION (DG) ON FEDERAL UNIVERSITY OF TECHNOLOGY (FUTA) 33/11 kV NETWORK | en_US |
| dc.type | Thesis | en_US |